Complete transformer substation KTPNB-6 (10) - analogue VLB-6 (10)

Vendor code 11921

0.0
Rate the product

0 reviews

Price Price on demand

Description

* for sectioning and ringing high-voltage lines 6 and 10 kV with two-way power supply to consumers of category I * special constructive solution for use at the enterprises of oil production and refining * equipped with vacuum circuit breakers VBP-10 with a spring-magnetic drive * modern types of RZIA systems (MOT, MTZ, AR) are provided, as well as mechanical and electrical interlocks from personnel erroneous actions * possibility of selling commercial and technical electricity metering systems

Characteristics

Rated voltage of power and control circuits, V
-220
Operating temperature, C
from -40 to +40
Overall dimensions (WxDxH), mm
1650х1406х4382
40000 (150)
Service life, years
25
Rated voltage (highest operating voltage), kV
6 (7,2); 10 (12)
Weight, kg
1270
Rated breaking current, kA
20
Rated current of main circuits, A
630