Description
Smoke detector optic-electronic address-analogue IP 212-64 prot.R3 is designed to detect fire, accompanied by the appearance of smoke of small concentration inside the monitored space in enclosed spaces of various buildings and structures and the transmission of the signal "Fire" to the receiving and monitoring device "Rubezh- 2ОП »prot.R3.
SPECIFICATIONS
Power supply from ALS (24-36 V)
Sensitivity of the detector is 0.05 to 0.20 dB / m
The detector remains operational when exposed to:
air flow with the speed of background illumination from artificial or natural light sources
up to 10 m / s up to 12,000 lux
The frequency of blinking of the light indicator in standby mode / in the "Fire" mode is 0.2Hz / 2Hz
Overall dimensions of the detector with a socket, not more than
Ø94 × 46 mm
Weight of the detector with a socket, not more than 120 g
Operating temperature range from minus 30 to plus 70 ° С
specialist. Ex. from minus 40 to plus 70 ° С
Average service life, not less than 10 years
Similar products
Volume burglar optical-electronic passive addressable detector IO 40920-2
- Vendor code
- 3078
Price Price on demand
Control modules for smoke exhaust or fire-retardant damper - MDU-1 PROT.R3, MDU-1S PROT.R3
- Vendor code
- 3079
Price Price on demand
Supporting stagger for installation of wooden supports RPN-20-630-59 supporting
- Vendor code
- 2271
Price 32.58 USD